Description |
This quick permit is to relocate existing horn/strobes and add two new strobe only devices to an existing NAC to accomodate a tenant remodel. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD11-02036 (HP BLDG B1 - RESTROOM RENNOVATION) This permit is for the up grade of eight restrooms four mens and four womens all in bldg 1. Four on the second floor and four on the first floor. the 1st floor ne wonens will also have the showers upgaded.
|