Permit Information
Permit NumberFIR11-00550
StatusFinaled
Name TAYLOR BROTHERS FIRE & SAFETY INC
Site Address 1555 W FRANKLIN ST
Project NameFRANKLIN PLAZA
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to replace the existing fire alarm system to accommodate elevator recall/shunt functions. This permit scope of work includes a manual fire alarm system, elevator recall/shunt functions, fire pump monitoring, sprinkler system monitoring, full notification, a smoke above the FACP, and non-required heat detectors next to all in-unit sprinkler heads. No HVAC has been indicated on the plans. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/27/20123/1/20123/2/2012PPASS
DetailsForrest France
Balance of acceptance test items completed. Corrections finished. Fire alarm permit finaled.
INSP-Final Inspection2/27/20122/29/20123/1/2012PPART
DetailsForrest France
Completed device testing at all tenant rooms on the 1st thru 5th floors including ADA rooms and notification appliances in common and public areas. Items noted include four HD to be replaced, one tenant denied access for inspection purposes, cd settings at ADA rooms need adjusted. Provide as-built drawings.
INSP-Final Inspection2/23/20122/24/20122/24/2012PPART
DetailsForrest France
Completed satisfactory retest of the elevator control functions after repairs made including the lobbies, pit and hoistway devices. Also finished acceptable testing of fire sprinkler monitoring including floor control valves, fire pump, MP station.
INSP-Alarm Testing2/23/20122/23/20122/24/2012APART
DetailsForrest France
INSP-Final Inspection2/17/20122/22/20122/22/2012PNR
DetailsForrest France
robert - elevator final only Phone #: ###-#### * Rescheduled due to elevator malfunction during inspection *410
INSP-Final Inspection2/14/20122/15/20122/16/2012PDEFR
DetailsForrest France
INSP-Alarm Testing2/13/20122/13/20122/13/2012APART
DetailsForrest France
Ref. plan annotations
INSP-Final Inspection2/9/20122/10/20122/10/2012PPART
DetailsForrest France
Completed initial walkthrough. Noted items include two old system HD and five lobby SD to be removed, provide signage at the door to the FACP room, need lock at the control panel breaker, trash chute may require heat detection devices.
INSP-Final Inspection2/3/20122/6/20122/7/2012PNR
DetailsForrest France