Permit Information
Permit NumberFIR11-00556
StatusFinaled
Name TAYLOR BROTHERS FIRE & SAFETY INC
Site Address 700 W CUNNINGHAM PL
Project NameCAPITOL PLAZA
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to replace the existing fire alarm system to accommodate elevator recall/shunt functions. This permit scope of work includes a manual fire alarm system, elevator recall/shunt functions, fire pump monitoring, sprinkler system monitoring, full notification, a smoke above the FACP, and non-required heat detectors next to all in-unit sprinkler heads. No HVAC has been indicated on the plans. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/27/20123/1/20123/2/2012PPASS
DetailsForrest France
Remainder of correction items verified for completion. Fire alarm permit finaled.
INSP-Final Inspection2/17/20122/22/20122/22/2012PPART
DetailsForrest France
Completed satisfactory testing for the elevator control functions including machine room, hoistway and lobby SD and HD, shunt and control voltage monitor.
INSP-Final Inspection2/14/20122/17/20122/17/2012PPART
DetailsForrest France
Completed testing for fire sprinkler monitoring including all floor control manifolds and pump room devices. Items noted include one non-functional TS at the 4th floor and two pump bypass tampers to be replaced.
INSP-Final Inspection2/9/20122/13/20122/14/2012PPART
DetailsForrest France
Completed notification appliance testing 1st thru 7th floors, verified previous C/N items. Decibel levels at the 1st floor common restrooms exceed max. allowable- provide strobe only per plan at these locations. Verified visual coverage at all ADA rooms, provide WP appliances where noted.
INSP-Alarm Testing2/9/20122/9/20122/10/2012PPART
DetailsForrest France
Completed testing of room heat detection devices throughout the 1st to 7th floors including system SD at ADA rooms. Noted items include 4 HD to be replaced, sync issues on the 7th floor, insufficient cd settings at ADA room notification appliances, four units in which access was denied for inspection purposes.
INSP-Final Inspection2/3/20122/6/20122/8/2012APART
DetailsForrest France
Verified previous correction items. Some issues remain including coverage at the 2nd floor operations office, raceway at the 4th floor, old system lobby SD's still in place, lock at FACP breaker. Alarm, trouble and supervisory signals were tested- however the zone 4 (supervisory) signals were undefined at central station monitoring. Discussed items remaining, inspection schedule, etc.
INSP-Alarm Testing1/24/20121/24/20121/24/2012APART
DetailsForrest France
INSP-Final Inspection1/18/20121/20/20121/24/2012PPART
DetailsForrest France
Completed initial walkthrough. Noted items in need of adjustment, incompleted items such as the remote annunciator, record of inspection and testing forms, removal of old system horns, detectors, MP's. Discussed inspection schedule.
INSP-Final Inspection1/4/20121/5/20121/5/2012ANR
DetailsForrest France
Robert Phone #: ###-####