Permit Information
Permit NumberFIR11-00571
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 5200 S FEDERAL WAY
Project NameNashua Addition
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of addition to an existing building. In addition, a portion of the roof will be raised. A new backflow preventer is being added. The system utilizes ELO sprinklers. The new portion and the portion with the raise roof is a compound grid. The existing portion is a standard grid. Both grids are interconnected as one system. The existing underground is 8” The riser and new backflow preventer is 8”. The branch piping is 2” and the mains are 6”, 5” and 4”. The system is based on extra hazard group II. The building is premanufacture of Z purlin construction.


Building Department Scope:

Nashua Manufacturing Building Addition - To construct a new 9,160 square foot, one, story manufacturing building addition at the northeast corner of an existing 26,265 square foot manufacturing building. The building addition and existing building are pre-engineered metal buildings. This permit also includes related site improvements. This building is fully fire sprinkled. The sprinklers are used for area increase. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/27/201112/28/201112/28/2011APASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Final Inspection12/23/201112/23/201112/23/2011PPART
DetailsForrest France
INSP-Final Inspection12/22/201112/22/201112/22/2011PPART
DetailsForrest France
Verified correction items, completed forward flow, final pending control valve tampers.
INSP-Final Inspection12/13/201112/14/201112/14/2011PNR
DetailsForrest France
Charles is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in12/14/201112/14/201112/14/2011AFAIL
DetailsForrest France
Noted items include #3, 5 and 7 on the fire code review comments regarding seismic brace attatchments to Z purlins, trapeeze calculations, and supervised tamper control vavles at the new DCVA. Also noted missing lateral branch line restraints per NFPA 13 2010 9.3.6.4 and plan detail. The compressor room appears inadequately heated.
INSP-Sprinkler Rough-in/Hydro12/13/201112/14/201112/14/2011PPART
DetailsForrest France
Overhead hydrostatic test passed after temp. bypass of the PRV.