INSP-Final Inspection | 12/27/2011 | 12/28/2011 | 12/28/2011 | A | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Final Inspection | 12/23/2011 | 12/23/2011 | 12/23/2011 | P | PART |
Forrest France
|
|
|
|
INSP-Final Inspection | 12/22/2011 | 12/22/2011 | 12/22/2011 | P | PART |
Forrest France
|
|
|
Verified correction items, completed forward flow, final pending control valve tampers.
|
INSP-Final Inspection | 12/13/2011 | 12/14/2011 | 12/14/2011 | P | NR |
Forrest France
|
|
|
Charles is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 12/14/2011 | 12/14/2011 | 12/14/2011 | A | FAIL |
Forrest France
|
|
|
Noted items include #3, 5 and 7 on the fire code review comments regarding seismic brace attatchments to Z purlins, trapeeze calculations, and supervised tamper control vavles at the new DCVA. Also noted missing lateral branch line restraints per NFPA 13 2010 9.3.6.4 and plan detail. The compressor room appears inadequately heated.
|
INSP-Sprinkler Rough-in/Hydro | 12/13/2011 | 12/14/2011 | 12/14/2011 | P | PART |
Forrest France
|
|
|
Overhead hydrostatic test passed after temp. bypass of the PRV.
|