Information based on query as of Friday, July 11, 2025.
Permit Information
Permit NumberFIR11-00650
StatusFinaled
Name TRI STATE ELECTRIC
Site Address 1211 S COLE RD
Project NameLDS TEMPLE
Customer Number 
ePlanReviewNo
Description
8/27/12 Plan Modification (no initiating devices affected): This plan modification is to incorporate field modifications and previous plan review redlines and comments. In addition, per the State Elevator Inspector, the two existing elevators are not required to have recall or shunt trip operations so the monitor modules and control modules for those functions have been deleted.
1/12/12: NOTE: A plan modification is required to be submitted and approved prior to calling for a final inspection.
This fire alarm permit is to replace the existing fire alarm system. This permit includes providing sprinkler system monitoring, elevator recall, HVAC monitoring/shutdown, a full manual system, and full notification throughout the building.
Associated building permit: BLD10-02069
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/6/20129/6/20129/6/2012PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection8/31/20129/5/20129/5/2012AFAIL
DetailsTroy Cobbley
NFPA 72 form is not completely filled out.
INSP-Final Inspection8/31/20129/4/20129/4/2012AFAIL
DetailsTroy Cobbley
Repair the PIV, provide notification in the basement dressing rooms, provide activation for the fire/smoke damper in the elevator room wall and provide as-builts which include the address changes, additional devices with revised EOL and voltage calculations.
INSP-Final Inspection8/29/20128/31/20128/31/2012ANR
DetailsForrest France
Pending corrections.
INSP-Final Inspection8/29/20128/30/20128/30/2012APART
DetailsForrest France
Completed initial walkthrough of the basement, first floor and mechanical mezzanine areas. Items noted include; missing lock and labels at the panel breakers, need to relocate the SD at the FACP, provide signage at the door to the FACP room, relocate MP at the riser, include added FSD at the elevator machine room on record drawings, provide missing occupant notification at the pantry locker/dressing room and the shop RR, replace ceiling mount horn at the chiller, need to verify min. dB is met at the storage rooms, visual coverage at the mens and womens dressing rooms 010 and 012 may be insufficient, provide strobe at the NW womens locker WC, provide coverage or a separation door at closet 109, instruction room 161 cd settings revised while on site, a/v at the brides room relocated to the opposite wall, "storage" room 196 will need occupant notification due to change in room use, need to verify dB measurements at the mechanical mezzanine and listing for concealed a/v's on the first floor.
INSP-Final Inspection8/29/20128/29/20128/29/2012PCANC
DetailsTroy Cobbley
overbooked
FIR-Aging Inspection6/13/20126/13/20126/20/2012 NR
DetailsTroy Cobbley
work is in progress