INSP-Final Inspection | 3/29/2012 | 3/29/2012 | 3/29/2012 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled. EOL voltages verified.
|
INSP-Alarm Testing | 3/28/2012 | 3/29/2012 | 3/29/2012 | A | PASS |
Troy Cobbley
|
|
|
Testing complete
|
INSP-Alarm Testing | 2/3/2012 | 2/6/2012 | 2/3/2012 | A | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
|
INSP-Sprinkler Rough-in/Hydro | 2/3/2012 | 2/6/2012 | 2/3/2012 | A | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
|
INSP-Alarm Testing | 1/20/2012 | 1/23/2012 | 1/23/2012 | A | FAIL |
Troy Cobbley
|
|
|
A minimum reading of 19.6 volts could not be verified with the volt meter and it appears that there are more than three strobe rates.
|
INSP-Sprinkler Rough-in/Hydro | 1/20/2012 | 1/23/2012 | 1/20/2012 | A | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
|
INSP-Sprinkler Rough-in/Hydro | 1/19/2012 | 1/20/2012 | 1/20/2012 | A | DONE |
Troy Cobbley
|
|
|
This was a pre-inspection. I found strobe coverage overspaced off of the breakroom wall. I discussed the need for EOL voltage verification.
|