Permit Information
Permit NumberFIR11-00688
StatusFinaled
Name ENTERPRISE ELECTRIC
Site Address 11311 W CHINDEN BLVD
Project NameHP BLDG 7 LOWER CTSL LAB
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide a new NAC panel and new notification devices to accommodate a tenant remodel involving the addition of rows of high server racks. The new NAC panel is to be located on the mezzanine. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/29/20123/29/20123/29/2012PPASS
DetailsTroy Cobbley
Permit finaled. EOL voltages verified.
INSP-Alarm Testing3/28/20123/29/20123/29/2012APASS
DetailsTroy Cobbley
Testing complete
INSP-Alarm Testing2/3/20122/6/20122/3/2012ACANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
INSP-Sprinkler Rough-in/Hydro2/3/20122/6/20122/3/2012ACANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
INSP-Alarm Testing1/20/20121/23/20121/23/2012AFAIL
DetailsTroy Cobbley
A minimum reading of 19.6 volts could not be verified with the volt meter and it appears that there are more than three strobe rates.
INSP-Sprinkler Rough-in/Hydro1/20/20121/23/20121/20/2012ACANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
INSP-Sprinkler Rough-in/Hydro1/19/20121/20/20121/20/2012ADONE
DetailsTroy Cobbley
This was a pre-inspection. I found strobe coverage overspaced off of the breakroom wall. I discussed the need for EOL voltage verification.