Permit Information
Permit NumberFIR11-00691
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 11311 W CHINDEN BLVD
Project NameHP BLDG 6
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of removing all pendent sprinklers in partial areas of two levels in building 6 and revising the upright sprinklers to have total coverage. The two levels will be changed back to a vanilla shell without occupancy. The western portion of the lower level (basement) is designed for Ordinary Hazard Group I. The remainder of the lower level and the second level (main) is designed for Ordinary Hazard Group II.

Plan Mod #1
General revisions based on actual field installation.


Building Department Scope:

(HEWLETT PACKARD)(BLDG 6 FAB - INTERIOR DEMOLITION & REPAIR) Select interior demolition work to change approximately 23,200 sq. ft. in the basement plus 28,200 sq. ft. on lower level and completely remove 1,024 sq. ft. of mechanical mezzanine, a total of 52,428 sq. ft. of existing 160,000 sq. ft., 2 level building (approx. 80,000 sq. ft. per level) back into vanilla shell and core space for future tenants per approved plans. Former use of the area of this scope of work was a fabrication facility. The work area is located on the south half of the building from the interior corridor south wall to the exterior south wall of the building and from the east side of the existing 2-hour area separation wall to the grid line S & S.5 on the plans. Work to include removal or modification of equipment, electrical, mechanical, plumbing, fire sprinkler and alarm systems; infill of openings in concrete created by removal of equipment; interior finish of damaged areas; restoration and maintenance of the fire-life in preparation for future tenant. NOTE: This building is fully fire sprinklered for allowable area increase. The existing 2-hour area separation wall along grid line C.5 up through the building created HP#6 East & HP#6 West, providing code compliance with allowable area for type of construction for the mixed use occupancy. All existing rated assemblies as indicated on plans are to be maintained. No additional interior work is allowed under this permit and no occupancy or use is being established. Separate plans, application, approval and permits are required for any future tenant improvements or occupancy of the indicated floor areas. Separate fire sprinkler plans and permits and alarm plans and permits are required as regulated by the Boise Fire Department. All fire and life safety systems (exiting, sprinklers, alarms, etc.) shall be maintained operational at all times during this scope of work unless specifically approved by the fire department. Drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/7/20123/7/20123/7/2012PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection3/2/20123/5/20123/5/2012AFAIL
DetailsTroy Cobbley
The south most basement branchline has upright sprinkler heads that are blocked by beams that have been wrapped in sheet rock. It appears that by turning the branchlines and installing pendants that most of the problem will be fixed. Also on this same branchline the southwest end head is located too far from the wall but relocating it closer to the wall will fix this problem as long as 130 sq. ft. is not exceeded. I will need as-built drawings showing these changes prior to a final sign off.
INSP-Final Inspection3/1/20123/2/20123/2/2012ADEFR
DetailsForrest France
Overbooked
INSP-Final Inspection2/15/20122/16/20122/16/2012AFAIL
DetailsTroy Cobbley
Inspection was stopped after issues found with the pipe sizing on the plans as compared to what was installed/existing. This includes piping in the remote areas and out side of the remote areas. I also found additional elbows and risers nipples on one branchline. Plans need to be modified to show actual pipe sizing and fitting counts and submitted for review.