Permit Information
Permit NumberFIR12-00013
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 10272 W ALPINE MEADOW ST
Project NameLagunas Residence
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of residential NFPA 13D system for a new home. The underground is polypipe installed by the fire protection contractor. The exposed riser and main in the garage is steel pipe. The remainder of the fire protection piping is CPVC. The piping is to be installed in the attic space and then tented to prevent freezing. An 1½” double check backflow preventer will be installed in the garage.



Building Department Scope:

***FIRE SPRINKLERS REQUIRED*** This permit is for the construction of a new 3480s.f. 2-story single family dwelling with 2703s.f. on the main level and 777s.f. on the upper level that extends over the 937s.f. 3-car garage. Separate electrical, plumbing, mechanical and ESC permits are required. R-1C ok per David Moser. All per the approved plans as marked, Energy prescriptive component method, ACCA report along with the plan review notes. Pep
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/4/20125/4/20125/4/2012PPASS
DetailsForrest France
UG flush, flow switch test and final walkthrough passed. Permit finaled.
INSP-Sprinkler Rough-in/Hydro2/28/20122/29/20122/29/2012PPASS
DetailsTim Frost
Rough in was ok. Plastic, was spread over the piping but there was no insulation. One bathroom had changed. There will be a pocket door that separates the area. In essecence, the are will become to small bathrooms which do not require sprinklers.
INSP-Supply line flush1/26/20121/26/20121/26/2012PPART
DetailsTroy Cobbley
Rough to cover the underground passed. Underground flush was not performed.
INSP-Supply line flush1/19/20121/20/20121/20/2012PFAIL
DetailsTroy Cobbley
The underground supply line is not buried deep enough, has been installed as 1 1/2" without the 2" starter and is not a continous run to the riser as shown on the plans.