INSP-Final Inspection | 8/31/2012 | 9/4/2012 | 9/4/2012 | A | PASS |
Forrest France
|
|
|
C/N items verified for completion. Fire alarm permit finaled.
|
INSP-Final Inspection | 5/14/2012 | 5/17/2012 | 5/17/2012 | A | FAIL |
Troy Cobbley
|
|
|
Smoke detector and manual pull station have been installed. Netcon was at an acceptable level of 5, all signals reported to central station. However, the alarm signals (pull station and water flow) did not intiate an audible alarm at the panel (required by NFPA 72 10.7). The smoke detector was not tested.
|
INSP-Final Inspection | 3/30/2012 | 4/2/2012 | 4/2/2012 | A | NR |
Forrest France
|
|
|
Existing system is not equipped with a MP or SD at the panel.
|