Permit Information
Permit NumberFIR12-00146
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 4175 S BROADWAY AVE
Project NameTravel Centers of America
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide an automatic detection system due to high-piled storage for tires. This scope of work includes smoke detectors in the high-piled storage area, and notification throughout the warehouse area.
Associated building permit: BLD12-00508
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/26/20133/27/20133/27/2013PPASS
DetailsForrest France
Correction items field verified for completion. Fire alarm permit final approved.
INSP-Final Inspection3/20/20133/22/20133/22/2013PPART
DetailsForrest France
Refer to plan review comments items #12 and plan modification comments #23 and 24 regarding adjustments to be made. New HD's at the truck bays okayed.
FIR-Aging Inspection2/4/20132/4/20132/5/2013 DONE
DetailsForrest France
Pending modifications
FIR-Aging Inspection9/27/20129/27/201210/3/2012 PEND
DetailsForrest France
INSP-Conference6/27/20126/27/20126/28/2012ADONE
DetailsForrest France
Conversation with contractor regarding NFPA 72 2010 23.8.5.4.1, 23.8.5.4.3 and IFC requirements for automatic smoke detection system at high piled storage.
INSP-Final Inspection6/25/20126/26/20126/26/2012APART
DetailsForrest France
Completed new system acceptance testing. Final pending as-built plans to include revised location of the FACP, SD, and MP, post signage at the door to the control panel room, provide points map at the panel. Tenant has requested alternate proposals to the system design in order to reduce possibility of false alarms due to environmental conditions at the truck repair bays.