INSP-Final Inspection | 3/26/2013 | 3/27/2013 | 3/27/2013 | P | PASS |
Forrest France
|
|
|
Correction items field verified for completion. Fire alarm permit final approved.
|
INSP-Final Inspection | 3/20/2013 | 3/22/2013 | 3/22/2013 | P | PART |
Forrest France
|
|
|
Refer to plan review comments items #12 and plan modification comments #23 and 24 regarding adjustments to be made. New HD's at the truck bays okayed.
|
FIR-Aging Inspection | 2/4/2013 | 2/4/2013 | 2/5/2013 | | DONE |
Forrest France
|
|
|
Pending modifications
|
FIR-Aging Inspection | 9/27/2012 | 9/27/2012 | 10/3/2012 | | PEND |
Forrest France
|
|
|
|
INSP-Conference | 6/27/2012 | 6/27/2012 | 6/28/2012 | A | DONE |
Forrest France
|
|
|
Conversation with contractor regarding NFPA 72 2010 23.8.5.4.1, 23.8.5.4.3 and IFC requirements for automatic smoke detection system at high piled storage.
|
INSP-Final Inspection | 6/25/2012 | 6/26/2012 | 6/26/2012 | A | PART |
Forrest France
|
|
|
Completed new system acceptance testing. Final pending as-built plans to include revised location of the FACP, SD, and MP, post signage at the door to the control panel room, provide points map at the panel. Tenant has requested alternate proposals to the system design in order to reduce possibility of false alarms due to environmental conditions at the truck repair bays.
|