Permit Information
Permit NumberFIR12-00177
StatusFinaled
Name R M E INC
Site Address 5777 N MEEKER AVE
Project NameBODYBUILDING.COM
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to remove all fire alarm devices and wiring, installing a new FACP, pull station, and smoke detector above the panel, remote annunciator panel, and re-connecting the existing sprinkler monitoring. This scope of work includes HVAC monitoring/shutdown, freight elevator recall and shunt trip functions, and sprinkler system monitoring. A DSC communicator is being used instead of phone lines.
Associated building permit: BLD12-00412
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/14/20138/15/20138/15/2013APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection8/13/20138/14/20138/14/2013AFAIL
DetailsTroy Cobbley
Basement fire alarm is complete (smoke detector was relocated and pull station lowered for my return trip). First floor fire alrm is complete (except updated as-builts are needed showing one additional in-duct detector). Second floor fire alarm is almost complete (Need to test all duct detectors, add two a/v's as marked on the plans)
INSP-Alarm Testing8/6/20138/8/20138/8/2013AFAIL
DetailsTroy Cobbley
Inspection was for an elevator test but I could not perform the test since the monitoring was not set up yet. I then did a walk through of the first and second floors to verify a/v spacing. I found many a/v's are overspaced most of which were in the restrooms. Many a/v's are missing/have not been installed. The multiple rooms in the Kitchen Area are not built yet and notification has not been installed. The Copy Room has been changed into an office and the a/v deleted. Most of the 15cd a/v in the corridors are mounted above 10' which is too high. Per the installed 12 in-duct detectors have been added. The main elevator, per the contractor, is being "grand fathered" by the state of Idaho and will not be required to have recall as shown on the plans. I did not inspect the basement. Plan modifications are required prior to additional inspections and final sign off.
FIR-Aging Inspection8/6/20138/6/20138/6/2013 NR
DetailsTroy Cobbley
work is in progress
FIR-Aging Inspection5/7/20135/7/20135/8/2013 NR
DetailsTroy Cobbley
Work is in progess
FIR-Aging Inspection2/5/20132/5/20132/13/2013 NR
DetailsTroy Cobbley
FIR-Aging Inspection9/28/20129/28/20129/28/2012 NR
DetailsTroy Cobbley
Per Clint the project is currently suspended but might possibly start back up.