Permit Information
Permit NumberFIR12-00198
StatusFinaled
Name TRI STATE ELECTRIC
Site Address 455 S BROADWAY AVE
Project NameWalgreen's
Customer Number 
ePlanReviewNo
Description
8/29/12 PLAN MODIFICATION (1 initiating device affected): This plan modification is to incorporate building floorplan changes, relocate the fire alarm panel and related smoke detector from the sprinkler riser area to an electrical equipment room, and provide a second duct detector.
4-20-12: This fire alarm permit is to provide a sprinkler monitoring system and a voluntary manual fire alarm system. This scope of work includes a pull station, a smoke detector, a remote annunciator panel, monitoring for the sprinkler system, a duct detector for HVAC shutdown/monitoring, and notification throughout the building.
Associated building permit: BLD11-01696
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/5/201210/5/201210/5/2012PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection10/4/201210/5/201210/5/2012AFAIL
DetailsTroy Cobbley
Provide map at the facp with a legend so the responding fire dept. can interpret the map, provide as-built floor plan that is to scale (as the original submittal), provide NFPA 72 record of completion forms.
INSP-Final Inspection10/2/201210/4/201210/4/2012ANR
DetailsForrest France
Need to adjust cd setting at the electrical room, relocate one device at the pharmacy, provide as-built plans for added PIV and notification at the pharmacy, post map and signage at the FACP, provide record of inspection and testing report.
FIR-Aging Inspection10/2/201210/2/201210/3/2012 DONE
DetailsForrest France
Inspection scheduled 10/3.