Permit Information
Permit NumberFIR12-00266
StatusFinaled
Name CURTIS FIRE SPRINKLER SERVICE INC
Site Address 12542 W FAIRVIEW AVE
Project NameSOCKEYE BREW PUB SHELL
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of 6”x24’± of underground through a 4” backflow preventer to a 4” header. The header has a3” wet system and a 2½” dry system. The dry system supplies the outside canopy. The tree type wet system has a 3” main with telescoping branch piping. The building for the most part has exposed open wood joist construction. The building will be used a combinations distillery and restaurant
Contractor’s Note:
The building permit has not been issued at this time. The building department may determine that changes are required to the building plans in order to meet code. The changes may affect the sprinkler system. The sprinkler contractor will be obligated to make all necessary changes that may be required. Therefore, if the sprinkler contractor chooses to proceed without an issued building permit, they will do so on their own cognizance. This note does not constitute an early start agreement.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/12/20129/12/20129/12/2012PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection9/10/20129/11/20129/12/2012PFAIL
DetailsTroy Cobbley
Provide pressure relief valve. Forward flush passed.
INSP-Sprinkler Rough-in/Hydro8/22/20128/22/20128/22/2012PPASS
DetailsTroy Cobbley
wet system hydro passed
INSP-Sprinkler Rough-in/Hydro8/21/20128/21/20128/21/2012PFAIL
DetailsTroy Cobbley
The wet system hydro test failed due to visable pressure loss at the guage. Sprinkler coverage has been provided in the future kitchen area and pendant heads have been modified as discussed in the future restraunt restrooms.
INSP-Sprinkler Rough-in8/13/20128/13/20128/13/2012PPASS
DetailsTroy Cobbley
Overhead/hydrostatic test for both wet and dry systems passed.