Permit Information
Permit NumberFIR12-00274
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 3415 N COLE RD
Project NameHobby Town
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of changing all pendent sprinklers to quick response. A couple of new small branch lines are being added in the western portion of the drawing. Most of the sprinklers are being relocated to accommodate new wall and ceiling configuration. Three existing tenant spaces are being combined into one space. The existing system is designed as three small trees. A new occupancy permit is required.

FIELD INSPECTOR: The building department scope of work does not correlate with the scope of work indicated on the fire protection plans. Therefore, please, do not approve the certificate of occupancy until the entire sprinkler system within the building department scope of work has been inspected and approved. You may of course approve the fire permit for the scope of work shown on the fire protection drawings if it is acceptable.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/3/20128/3/20128/3/2012PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in7/10/20127/10/20127/10/2012PPASS
DetailsTroy Cobbley
Sprinkler piping can be covered.
INSP-Conference7/9/20127/10/20127/10/2012ADONE
DetailsTroy Cobbley
Sprinkler piping is ok to cover.
INSP-Conference7/9/20127/9/20127/9/2012PDONE
DetailsTroy Cobbley
Ceiling is ok to install from the west wall to the first column line.
INSP-Final Inspection7/9/20127/9/20127/9/2012PFAIL
DetailsTroy Cobbley
Inspection was actually a conference on what is required to fix the insulation blocking the upright sprinkler heads. We went over the NFPA 13 obstruction charts.
INSP-Sprinkler Rough-in7/3/20127/5/20127/5/2012APART
DetailsTroy Cobbley
Upright coverage has been added but the insulation blockage issue has not been addressed yet. Piping can not be covered yet.
INSP-Sprinkler Rough-in6/27/20126/28/20126/28/2012APART
DetailsTroy Cobbley
Rough-in, for pendant sprinklers, for the most part is ok. Almost all of the upright sprinklers are blocked by hanging insulation. Also Mike and I found one location where upright heads are overspaced from an existing wall and some of the existing upright heads are blocked by duct work. These two items will need to be addressed prior to an approval for cover being given.