Permit NumberFIR12-00318
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 4111 W OVERLAND RD
Project NameAUTOZONE
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of providing fire sprinkler protection for and existing portion of the building, which is mercantile, and a new portion of the building, which is storage. There is one system divide into two grids. The grid in the existing portion is 3”x3”x1½”. The grid in the new portion is 6”x4”x3”. The system is supplied through approximately 8”x140”± C-900 underground piping with associated fittings and restraints. The riser is equipped with a 6” backflow preventer. The existing mercantile portion of the system utilizes extended coverage 16’x16’ standard response sprinklers. The new portion utilizes CMSA with 14’x14’ spacing. The new portion has 16’ high racks with an intermediate catwalk level. The storage on the racks has been considered as Class IV. The design is based on FM 8-9 and 2-0 since there was not any criterion per NFPA for this particular rack, mezzanine, and catwalk configuration. Therefore, IFC:102.8 was utilized.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/29/201211/29/201211/29/2012PPASS
DetailsForrest France
Final walkthrough and inspection completed. Forward flow passed. Fire sprinkler permit finaled.
INSP-Final Inspection11/28/201211/28/201211/29/2012PNR
DetailsForrest France
Final pending project related fire alarm testing for riser supervision. Also need to complete forward flow test.
INSP-Sprinkler Rough-in/Hydro11/28/201211/28/201211/29/2012PPART
DetailsForrest France
Overhead hydrostatic test completed satisfactory. Need to add baffles per approved plan.
INSP-Sprinkler Rough-in11/13/201211/14/201211/14/2012APART
DetailsForrest France
Existing storeroom and stock area fire sprinkler work passed overhead rough-in inspection. Okayed for ceiling cover- see plans for dated annotations.
INSP-Sprinkler Rough-in11/8/201211/13/201211/13/2012ACANC
DetailsTroy Cobbley
Cancel per mike Phone #: ###-####
INSP-Sprinkler Rough-in10/29/201210/30/201210/31/2012PPART
DetailsForrest France
Overhead rough-in at the upper warehouse passed- see plans for dated annotations.