Permit NumberFIR12-00343
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 8901 W CANDLESTON LN
Project NameCandleston Four-Plex
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of protecting a four family residential building using NFPA 13R. The riser is a located in a separate outside room and is supplied by a 2” dedicated underground supply. The system has a 1½” feed main with 1” lines. The sprinklers are spaced at 20’x20’ except in the vaulted ceiling areas which are 16’x16’.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/4/201210/5/201210/5/2012APASS
DetailsTroy Cobbley
Permit finaled.
INSP-Sprinkler Rough-in/Hydro7/24/20127/24/20127/24/2012PPASS
DetailsTroy Cobbley
Hydro test passed for the overhead systems.
INSP-Sprinkler Rough-in7/23/20127/24/20127/24/2012APASS
DetailsTroy Cobbley
Tenting is passed. Sprinkler piping can be covered.
INSP-Sprinkler Rough-in7/19/20127/20/20127/20/2012PPASS
DetailsTroy Cobbley
Sprinkler rough-in passed. One pendant head still needed to be installed. One pendant head shown to be installed in the main level restroom has not been installed and doesn't need to be based on NFPA 13R 6.6.2. Piping can not be covered until the insulation/tenting is completed and inspected. An additional inspection will be required for this.