Permit Information
Permit NumberFIR12-00373
StatusFinaled
Name SONITROL PACIFIC
Site Address 7500 W MOSSY CUP ST
Project NameNxEdge
Customer Number 
ePlanReviewNo
Description
This quick permit scope of work is to provide notification in two existing clean rooms. The devices are to be added to an existing circuit. There are redlines on the plans. As-built drawings will be required at the time of final inspection. Approval is subject to field measurement of the EOL voltage drop. The voltage drop calculations are based on a 10% drop, therefore the minimum acceptable voltage is 21.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V (per UL 864, Standard for Control Units for Fire Signaling Systems). See NFPA 72 2010 Handbook 18.3.2.3 for further assistance with calculations.The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/4/20129/7/20129/7/2012PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing8/27/20128/27/20128/27/2012PFAIL
DetailsTroy Cobbley
One of the two strobes needed the candella increased to meet code while I waited. When the manual pull station was activated the horn strobes did not activate. Inspection failed. Also need updated as-builts showing the relocated strobe and the one with the increased candella.
INSP-Final Inspection8/21/20128/24/20128/24/2012PCANC
DetailsTroy Cobbley
Chris and I agreed to reschedule this test for monday afternoon since I am overbooked.