Permit Information
Permit NumberFIR12-00412
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 300 S BROADWAY AVE
Project NameChick-Fil-A Restaurant -
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of above and below protection for a new restaurant. The main supply has 151’± 6” C-900 underground pipe, fittings and thrust blocks into a fire riser room with an outside entrance. The main riser has a 3” back flow preventer, 3” FDC and supplies a small antifreeze system for the decorative towers. The fire protection configuration is a tree system with 3” main and telescoping branch piping.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/15/201210/15/201210/16/2012PPASS
DetailsForrest France
Overhead fire sprinkler work passed final inspection and walkthrough.
INSP-Sprinkler Rough-in/Hydro9/20/20129/20/20129/20/2012PPART
DetailsForrest France
Overhead hydrostatic test of the wet and antifreeze systems passed.
INSP-Sprinkler Rough-in9/19/20129/19/20129/19/2012PPART
DetailsForrest France
Overhead rough-in including the wet and antifreeze system is approved for cover. Noted two painted pendent heads in need of replacement, discussed construction rating of the riser room with the general contractor.
INSP-Sprinkler Rough-in8/21/20128/21/20128/21/2012PPART
DetailsForrest France
Overhead work at the mens and womens restroom, yard service, and west entry vestibule/soffit are okay to cover. Locations marked and dated on plans.