Permit Information
Permit NumberFIR12-00431
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 5369 W IRVING ST
Project NameJR Simplot Lab Bldg. A
Customer Number 
ePlanReviewNo
Description
11/7/12 Plan Modification (5 initiating devices affected): This plan modification is to include two duct detectors not shown on the original plans (2nd floor), revise the make/model of the remote power supplies, include release functions/devices for two mag lock locations on general alarm, and to incorporate the redlines/review comments from the original review.
8/21/12: This fire alarm permit is to extend an existing non-required manual fire alarm system in an existing building. This permit scope of work includes adding and/or relocating notification devices, new smoke detectors above the panels, modules to monitor the existing Ansul system for alarm and trouble signals, and new duct detectors w/remote test switches for HVAC monitoring/shutdown. This building also has an existing AES RF radio for communications with the central station.
Associated building permit: BLD11-03012
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/13/201211/14/201211/14/2012PPASS
DetailsTroy Cobbley
permit finaled
INSP-Alarm Testing11/7/201211/8/201211/8/2012APART
DetailsTroy Cobbley
A temporary occupancy was given until the fire alarm permit/correction issues have been addressed.
INSP-Final Inspection11/5/201211/6/201211/6/2012PCANC
DetailsTroy Cobbley
No testing was performed due to the plans needing resubmitted. I also noted door magnets that have been installed within the past week that are not connected to the fire alarm system as required per IFC 1008.1.4.4.
INSP-Final Inspection10/29/201210/29/201210/29/2012PFAIL
DetailsTroy Cobbley
All items tested except for the smoke detector over the main facp, duct smoke detectors and all notification items. Plans need to be resubmitted showing the correct NAC panels installed, audio/visuals have been added, candellas have been changed, audio/visual devices are overspaced and some are mounted too high. The manual pull station is mounted too high as well. Signals were verified through the Peak Alarm guard at the gate.