Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR12-00433
StatusFinaled
Name R M E INC
Site Address 7500 W FAIRVIEW AVE
Project NameWestgate Shopping Center
Customer Number 
ePlanReviewNo
Description
12/11/12 Plan Modification (7 initiating devices affected): This plan modification is to provide a DSC wireless transmitter instead of the DACT for communications to central station monitoring, providing new addressable relay modules for each duct detector to perform HVAC shutdown, show the duct detectors using 24V instead of 120V from the HVAC units, and to provide an addressable monitor module for loss of power to the DSC.
8/16/12: This fire alarm permit is to replace the existing fire alarm panel with new. This permit scope of work includes removal of the existing fire alarm panel and all wiring, placement of the new panel in Electrical Room 107, smoke detector above the panel, pull station, duct detectors for HVAC monitoring/shutdown, and modules for monitoring the wet and dry sprinkler systems
Associated building permit: BLD11-02833
NOTE: a remote annunciator is not required under this permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/16/201512/17/201512/17/2015APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection12/14/201512/16/201512/16/2015AFAIL
DetailsTroy Cobbley
Duct smoke detectors tested ok. FOr a final need as-builts submitted to lee for approval showing the different dialer and changed device counts and addresses. Also need to mount the map at the facp.
INSP-Conference10/26/201510/26/201510/26/2015PDONE
DetailsTroy Cobbley
Danielle with the propertry management company and I discussed getting the FIR12-00433 finaled prior to a final sign off on BLD15-03739. With Scott Arellano's permission the tenant can receive a temporary occupancy for 30 days while the contractors work towards getting the FIR permit finaled.
INSP-Final Inspection4/2/20134/3/20134/3/2013AFAIL
DetailsTroy Cobbley
The first hvac unit tested did not shutdown upon activation of the duct smoke detector so no others were tested. The DSC communicator installed is not the model number in the submittal package and will need to be submitted for approval. As-builts and map do not match the actual installation with additional devices shown that have not been installed and addressing changes. The sprinkler systems devices did test ok and the correct signals were received at central station.
INSP-Alarm Testing3/21/20133/25/20133/25/2013PNR
DetailsForrest France
INSP-Alarm Testing3/13/20133/15/20133/15/2013AFAIL
DetailsTroy Cobbley
The approved "plan modification" drawings are not provided, pull station is too high, batteries are too small, sample tubes are too short (per silent knight tech support), need as-builts showing the deleted devices, per conversation only one of the hvac unit shuts down immediately upon detection of smoke. No actual testing was performed.
FIR-Aging Inspection2/5/20132/5/20132/13/2013 NR
DetailsTroy Cobbley
I left a voice mail for Anita at ESI requesting job status and then I spoke to Buster at RME and he stated that there is a monitoring problem that they are waiting for ESI to resolve. I will speak to Anita when she calls.