Permit Information
Permit NumberFIR12-00490
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 113 S AUTO DR
Project NameCalvary Chapel
Customer NumberUDG ONLY
ePlanReviewNo
Description
The fire sprinkler scope of work consists of 6”x120’± C-900 underground piping and fittings with necessary thrust blocks and restraints.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/26/20138/27/20138/27/2013PPASS
DetailsTroy Cobbley
Permit finaled
FIR-Aging Inspection6/27/20136/27/20136/28/2013 DONE
DetailsTroy Cobbley
work is in progress
FIR-Aging Inspection2/19/20132/19/20132/20/2013 NR
DetailsTroy Cobbley
work is in progress
INSP-Sprinkler Rough-in/Hydro9/28/201210/1/201210/1/2012ACANC
DetailsTroy Cobbley
Need an Underground Hydro inspection 1st thing in the morning if possible - Brian Dunham is the contact at 570.0497 Phone #: ###-#### >> Inspection requested via web by Kindel de Leon Inspection cancelled from web by: Scott Carter II
INSP-Sprinkler Rough-in9/26/20129/27/20129/27/2012PPASS
DetailsTroy Cobbley
Underground supply line is ok to cover. I noted that two additional (four total) 45 degree fittings have been installed and will need to be included in the hydraulic calculations for the overhead sprinkler system.