Permit Number | FIR12-00511 |
Status | Finaled |
Name |
NORTHWEST SECURITY INC
|
Site Address |
7990 W OVERLAND RD
|
Project Name | Lowe's |
Customer Number | |
ePlanReview | No |
Description |
This quick permit is to relocate and existing horn/strobe from a room previously used as a manager's office to an ajoining new manager's office, and to relocate an existing pull station and remote annunciator from outside the new manager's office to the entry/battery area. Approval is subject to field measurement of the EOL voltage drop. the minimum acceptable voltage is 21.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V (per UL 864, Standard for Control Units for Fire Signaling Systems). See NFPA 72 2010 Handbook 18.3.2.3 for further assistance with calculations. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. There is no associated building permit.
|