Permit Information
Permit NumberFIR12-00528
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1527 W ALEXANDRA LN
Project NameLloyd Subdivision
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of providing a 13R system for one unit in a four-plex unit. The system utilizes CPVC piping with residential extended throw sprinklers. Each floor has a separate floor control valve. The system must be monitored per IFC requirements.

Multiple sprinkler rooms have been designed for 18’x18’ spacing.
Single sprinkler rooms have been design for 20’x20’ spacing.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/14/201212/17/201212/17/2012APASS
DetailsForrest France
Fire sprinkler work passed final walkthrough and inspection.
INSP-Final Inspection12/14/201212/14/201212/14/2012PCANC
DetailsForrest France
Mark J is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Sprinkler Rough-in11/1/201211/2/201211/2/2012APART
DetailsForrest France
Inspection for cold cavity protection completed okay after adjustments made while on site by the general contractor. Overhead rough-in approved for cover.
INSP-Sprinkler Rough-in/Hydro10/29/201210/30/201210/30/2012PPART
DetailsForrest France
OH hydrostatic test completed.