Permit Information
Permit NumberFIR12-00529
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1535 W ALEXANDRA LN
Project NameLloyd Subdivision
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of providing a 13R system for one unit in a four-plex unit. The system utilizes CPVC piping with residential extended throw sprinklers. Each floor has a separate floor control valve. The system must be monitored per IFC requirements.

Multiple sprinkler rooms have been designed for 18’x18’ spacing.
Single sprinkler rooms have been design for 20’x20’ spacing.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/3/201212/3/201212/3/2012PPASS
DetailsForrest France
Noted correction items completed, final walkthrough passed. Fire sprinkler permit finaled.
INSP-Sprinkler Rough-in/Hydro10/24/201210/25/201210/29/2012PPART
DetailsForrest France
Overhead rough-in approved for cover.
INSP-Sprinkler Rough-in/Hydro10/25/201210/26/201210/26/2012APART
DetailsForrest France
Overhead hydrostatic test completed acceptable including the FDC supply.
INSP-Sprinkler Rough-in10/24/201210/24/201210/24/2012PFAIL
DetailsForrest France
Overspaced heads at two locations, four open outlets, one end of line at the second floor needs tenting adjusted. See stamped plan set for marked areas.
INSP-Sprinkler Rough-in10/22/201210/23/201210/23/2012AFAIL
DetailsForrest France
Noted four pendent heads in need of relocation due to light fixture obstructions, heads at furnace closets to meet temp. ratings per 6.2.3.3.3, verify equipment at the exterior balcony rooms are not fuel-fired.