Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR12-00547
StatusFinaled
Name PEAK ALARM
Site Address 1477 S VINNELL WAY
Project NameCentury Landmark Center-Décor
Customer Number 
ePlanReviewNo
Description
11/1/12 Plan modification (4 initiating devices affected): This plan modification is to include four new monitor modules to monitor duct detectors for HVAC shutdown.
9/25/12:This fire alarm permit is to provide a fire alarm panel to monitor a new sprinkler system. This permit scope of work includes a pull station, a smoke detector, sprinkler system monitoring, and a remote annunciator. No HVAC has been indicated on the plans. Instead of a DACT, an AES RF radio is being provided.
Associated building permit: BLD12-02043
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/14/201211/14/201211/14/2012PPASS
DetailsTroy Cobbley
Permit finaled. The duct smoke detector power is now supplied from a separater 110 volt circuit and not from the fire alarm control panel.
INSP-Final Inspection11/8/201211/8/201211/8/2012PFAIL
DetailsTroy Cobbley
The new duct smoke detectors are powered from the fire alarm control panel which is not noted on the plans. Per the plan reviewer revised calculations are required showing the addtional power loss prior to a final sign off. HVAC units were tested for shutdown which passed.
INSP-Final Inspection10/19/201210/22/201210/22/2012PFAIL
DetailsTroy Cobbley
The electric alarm bell has not been installed yet. Plan modifications are required for the four duct smoke detectors that were not included on the original submittal. The sample tubes currently installed are too short. Need breaker lock installed. The manual pull station installed is not the same as the submittal though it is addressable and does function.