Permit Information
Permit NumberFIR12-00604
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 2284 S GEKELER LN
Project NameAeries Commons
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of protecting a 3-plex apartment building based on NFPA 13R. The system utilizes CPVC piping. The system has floor control valves located in an outside shed type building next to unit 2288. The sprinkler spacing varies based on the number of sprinklers in a compartment, 20’x20’ for one sprinkler, 16’x16’ for more than one. The piping in the attic will be tented. There is a 2”x20’ CPVC underground supply the system.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/7/20131/7/20131/7/2013PPASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Final Inspection1/3/20131/4/20131/4/2013PFAIL
DetailsTroy Cobbley
Need the spare heads/wrench for the head box and the backflow certified.
INSP-Sprinkler Rough-in/Hydro12/7/201212/7/201212/7/2012PPART
DetailsForrest France
Overhead hydrostatic re-test passed for both the first and second floors.
INSP-Sprinkler Rough-in/Hydro12/4/201212/5/201212/5/2012ACANC
DetailsTroy Cobbley
Cancel per Lonnie phone #: ###-####
INSP-Sprinkler Rough-in/Hydro12/4/201212/4/201212/4/2012PNR
DetailsForrest France
Guages below 200 psi. @ approx 190.
INSP-Sprinkler Rough-in/Hydro12/3/201212/3/201212/3/2012PFAIL
DetailsTroy Cobbley
Hydro test failed on both systems due to visable pressure loss.
INSP-Sprinkler Rough-in11/1/201211/1/201211/2/2012PPASS
DetailsTroy Cobbley
Tenting is complete. Piping is ok to cover.
INSP-Sprinkler Rough-in10/29/201210/29/201210/29/2012PPART
DetailsForrest France
Overhead rough-in inspection completed. Need to verify lintel or door at second floor bathroom to meet ft2 exception or install a pendent, missing sprinkler heads at two locations. Tenting to be inspected prior to approval for cover.