Permit NumberFIR12-00610
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 113 S AUTO DR
Project NameCalvary Chapel
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of protecting a new church. The system is a modified grid with 1¼” branch lines, 3”, 2” & 1¼” mains. The system is supplied through 6” underground piping, 3” riser with 3” backflow preventer.

Underground piping is under permit FIR12-00490
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/3/20139/4/20139/4/2013PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection8/29/20138/30/20138/30/2013ACANC
DetailsTroy Cobbley
Please call Perly 30 minutes prior Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt
INSP-Sprinkler Rough-in/Hydro8/28/20138/28/20138/28/2013PPASS
DetailsTroy Cobbley
OH Hydro passed
INSP-Sprinkler Rough-in/Hydro8/27/20138/27/20138/27/2013PFAIL
DetailsTroy Cobbley
Overhead hydro test failed due to visible pressure loss on the guage.
INSP-Sprinkler Rough-in/Hydro8/26/20138/26/20138/26/2013PCANC
DetailsTroy Cobbley
Overbooked
INSP-Sprinkler Rough-in8/16/20138/19/20138/19/2013APART
DetailsTroy Cobbley
Piping can be covered but several locations marked in red have upright sprinkler coverage overspaced due to insulation. Also several of the classroom closets have surface mounted light fixtures located right next to sprinkler heads. Ceiling tile will need to be removed to verify these corrections.
INSP-Sprinkler Rough-in5/28/20135/28/20135/28/2013PPASS
DetailsTroy Cobbley
The underground flush passed. Not ready for an additional cover inspection.
INSP-Sprinkler Rough-in5/8/20135/9/20135/9/2013APASS
DetailsTroy Cobbley
Hard lids ok to cover. I noed one location in the northwest corner of the building where upright sprinkler coverage is needed above one of the hardlids.
FIR-Aging Inspection3/15/20133/15/20133/15/2013 NR
DetailsTroy Cobbley
work is in progress