INSP-Final Inspection | 12/28/2012 | 12/31/2012 | 12/31/2012 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. Music shuts off upon activation of alarm.
|
INSP-Final Inspection | 12/28/2012 | 12/28/2012 | 12/28/2012 | P | FAIL |
Troy Cobbley
|
|
|
The music did not shut down/reduce as required. THis is the last remaining item prior to a final sign offf.
|
INSP-Final Inspection | 12/17/2012 | 12/17/2012 | 12/18/2012 | P | PART |
Troy Cobbley
|
|
|
A temporary occupancy is being given with Scott Arellano's permission until the Arcade/music reduction/shutdown has been installed and tested. This approval is only for the kitchen area.
|
INSP-Alarm Testing | 12/12/2012 | 12/13/2012 | 12/13/2012 | P | DONE |
Troy Cobbley
|
|
|
Provide accurate as-builts, provide breaker locks, provide map at the facp, provide shutdown/reduction of music/arcade machines as per NFPA 72 18.4.1.5, 18.4.3.5, relocate smoke detector to the deck at the facp. Signals verified for flow and tamper switches, hvac reporting and shutdown and kitchen hood suppression systems. Spacing verified for audio/visual devices. EOL verified as ok.
|