Permit Information
Permit NumberFIR12-00644
StatusFinaled
Name ALARMCO
Site Address 2108 S CENTURY WAY
Project NameQuality Thermistor
Customer Number 
ePlanReviewNo
Description
12/18/12 Plan Modification (no initiating devices affected): This plan modification is to replace the DACT with an IGSMCF digital cellular communicator. New notes regarding this modification are at the end of the review comments starting on page 7.
This fire alarm permit is to replace the existing ADT fire alarm panel and system with new. This permit scope of work includes sprinkler system monitoring, duct detector monitoring for HVAC shutdown, a remote annunciator panel at the main entrance, a smoke detector above the FACP, a manual pull station in the riser room, and two voluntary heat detectors in the oven room. There is no associated building permit. The DACT is being replaced with an IPGSM-DP fire alarm communicator with cellular backup.
12/5/12: The contractor resubmitted with using the onboard DACT rather than a different communications technology.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/28/20131/28/20131/28/2013APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection1/15/20131/16/20131/16/2013PFAIL
DetailsTroy Cobbley
Need a report of the signals sent today, as-builts showing the actual wiring of the dialer to the facp and verification sent to plan review to approve this wiring, and the duct smoke detectors repaired. Need signage on the facp room door as well.