Permit Information
Permit NumberFIR12-00645
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 980 N MILWAUKEE ST
Project NameMICKEY RAY'S BBQ RESTAURANT
Customer Number 
ePlanReviewNo
Description
1/16/13 Plan Modification (no initiating devices affected): This plan modification is to change the type of fire alarm control panel, eliminate the existing external power supply and its associated smoke detector, and to incorporate previous redlines and review comments.
11/13/12: This fire alarm permit is to remove existing non-required notification and pull stations and all associated wiring. To remain are the existing smoke detector above the FACP, an existing smoke detector above an existing remote power supply (located above the ceiling of Office 114), an existing pull station located at the sprinkler riser, monitoring the existing sprinkler system, monitoring for two existing hood suppression systems, monitoring existing duct detectors for HVAC shutdown, and an existing remote annunciator panel.
Associated building permit: BLD12-01915
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/4/20132/6/20132/6/2013APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection11/19/201211/20/201211/20/2012AFAIL
DetailsTroy Cobbley
The zone 6 still did not report within the required 90 seconds. I then verified the actual time on a general alarm and found that it did not report to the monitoring station within the 90 seconds either. The fire alarm system shall meet current timing requirements as per NFPA 72. A re-inspection fee has been applied to this job for any more inspections.
INSP-Final Inspection11/19/201211/19/201211/19/2012PFAIL
DetailsTroy Cobbley
The duct smoke detectors on zone 6 still are not reporting to the monitoring station.
INSP-Final Inspection11/16/201211/16/201211/16/2012PPART
DetailsTroy Cobbley
A temporary occupancy was given with Scott Arellano's permission until the correct programming of the duct smoke detectors is accomplished with the monitoring company. All other items have been corrected. The hvac units had not previously been wired for shut down but are now.
INSP-Final Inspection11/15/201211/16/201211/16/2012AFAIL
DetailsTroy Cobbley
The fire alarm control panel only has one phone line, monitoring is not set up correctly (no alarm or supervisory signals were received), hvac units did not shut down upon detection of smoke and as-builts are needed showing the additional tamper switch as well as the smoke detector above the ceiling.