Permit Information
Permit NumberFIR12-00666
StatusFinaled
Name CRANE ALARM COMPANY
Site Address 6945 W OVERLAND RD
Project NameD & B SUPPLY
Customer Number 
ePlanReviewNo
Description
1/3/13 Plan Modification #2 (no initiating devices affected): This plan modification is to incorporate field changes and previous redlines/review comments.
12/27/12 Plan Modification (no initiating devices affected): This plan modification is to replace the DACT with an AES RF radio. Please see additional notes starting on page 5 of this review.
11/28/12: This fire alarm permit is to replace the existing fire alarm system with new. This permit includes a required manual fire alarm system with full notification, a smoke detector, a pull station, sprinkler system monitoring, and HVAC system monitoring/shutdown.
Associated building permit: BLD12-02323
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/7/20131/7/20131/7/2013PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection12/31/201212/31/201212/31/2012PFAIL
DetailsTroy Cobbley
Plan modifications need to be submitted showing the actual wall layout, new devices/deleted devices and new circuits. Also include the correct model of duct smoke detectors used on the hvac units. I also will need the breaker identified and locked out, building map posted and NFPA 72 forms.
INSP-Final Inspection12/28/201212/28/201212/28/2012PFAIL
DetailsTroy Cobbley
Project is not ready for inspection. The system had not been turned on or pre-tested prior to inspection. I performed a walk around and noted on the city approved plans located where strobes are over spaced, have been added or deleted. It appears that strobes to the east of column line 8 will be blocked by racking that exceeds 6' in height. We did set off the audio/visuals after activating the panel and I found that neither the audio or visuals are sync'd. Per the fire alarm plans examiner due to small safety factor for the EOL voltages any changes will require a plan modification. Per Romeo it will be ok for the owner to stock if the fire alarm is inspected to verify that sprinkler and hvac monitoring is in place.