Permit Information
Permit NumberFIR12-00681
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 800 W MAIN ST
Project Name8th & Main Twr CoreBase & Pump
Customer NumberBASEMENT PUMP
ePlanReviewYes
Description
The fire sprinkler scope of work consists of the basement and fire pump. The fire pump is rated at 750 Gpm @ 175 Psi. There will be two 6” supplies to the fire pump and two FDC connections. The fire pump is equipped with a 6” by pass and 6” hose test header. The system layout for the basement consists of a pressure reducing valve (set at 125#) a 3” loop with 1¼” branch piping. All sprinklers are quick response type. The basement also has a 4” header with (3) 4” dry pipe valves for the 3-5 floors.

The underground is under permit FIR12-00605
The standpipes is under permit FIR12-00634
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/17/201312/17/201312/18/2013PPASS
DetailsForrest France
INSP-Final Inspection12/12/201312/13/201312/13/2013APART
DetailsForrest France
C/N items include matched temp heads at an electrical room, replace hanger on added coverage, access to NW elevator machine room, floor drain function at the fire pump room.
INSP-Final Inspection11/27/201312/2/201312/3/2013APART
DetailsForrest France
Need to remove valves in the pressure sensing lines per NFPA 20, pump room still missing ventilation, floor drain does not function, final walkthrough at the basement incomplete.
INSP-Final Inspection11/19/201311/22/201311/26/2013ANR
DetailsForrest France
Mike B is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in10/8/201310/10/201310/10/2013APART
DetailsForrest France
Completed fire pump acceptance testing per NFPA 20. Noted fire pump room is missing required ventilation, floor drain does not function adequately, upright heads at the new west wall exceed min. distance from the wall.
INSP-Sprinkler Rough-in/Hydro3/27/20133/29/20133/29/2013PPART
DetailsForrest France
For overhead hydrostatic testing of the header and supply piping.
INSP-Sprinkler Rough-in2/26/20132/27/20133/1/2013PPART
DetailsForrest France
Noted corrections at the basement level shell work only.