Permit Information
Permit NumberFIR12-00728
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 9543 W EMERALD ST
Project NameEmerald Bldg – Ste# A
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of adding, plugging and relocating sprinklers to accommodate new wall and ceiling configuration.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/11/20131/14/20131/14/2013APASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in1/11/20131/11/20131/11/2013PPASS
DetailsTroy Cobbley
Rough-in passed. Sprinkler piping is ok to cover.
INSP-Sprinkler Rough-in1/9/20131/9/20131/9/2013PFAIL
DetailsTroy Cobbley
Pipe sizing for the new branchline does not match plans or the hydraulic calculations. Also the first pendant head on this new line was not installed as per plan and as a result coverage is lacking at the office wall. Additional access needs to be provided to see all of the piping and hangers that are concealed above the ceiling.