Permit Information
Permit NumberFIR12-00741
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 6945 W OVERLAND RD
Project NameD & B SUPPLY @ OVERLAND PARK
Customer Number 
ePlanReviewYes
Description
INSTALL A NEW 3" LINE TO FEED THE NEW STORAGE ROOMS AT THE BACK OF THE BUILDING WITH EXTENDED COVERAGE DRY HSW'S. CALCULATIONS HAVE BEEN PROVIDED.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/18/20131/22/20131/22/2013APASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in/Hydro1/17/20131/17/20131/17/2013PPASS
DetailsTroy Cobbley
Overhead hydro and rough-in passed.
INSP-Sprinkler Rough-in/Hydro1/17/20131/17/20131/17/2013PFAIL
DetailsTroy Cobbley
Overhead hydro test for the new storage area piping failed due to visable drop on the pressure guage. Also the earthquake attachments do not match the city approved drawings and don't have through bolts for the wood members per NFPA 13 Chapter 9.
INSP-Sprinkler Rough-in/Hydro1/16/20131/16/20131/16/2013PCANC
DetailsTroy Cobbley
Canceled due to time constraints. jeremy Phone #: ###-####