Permit Information
Permit NumberFIR12-00744
StatusFinaled
Name CRANE ALARM COMPANY
Site Address 1450 S EAGLE FLIGHT WAY Unit: 125
Project NameQuail Court Ste# 125
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to extend the existing fire alarm system and notification in to the new tenant space.
Associated building permit: BLD12-03154
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/14/20133/15/20133/15/2013APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection1/16/20131/17/20131/17/2013PFAIL
DetailsTroy Cobbley
The audible notification devices are not synchronized as required per NFPA 72 18.4.2.5 . The tenant area new devices do not sync with the existing area corridor devices.
INSP-Final Inspection1/15/20131/16/20131/16/2013PCANC
DetailsTroy Cobbley
Cancel per tim Phone #: ###-####
INSP-Final Inspection1/8/20131/8/20131/8/2013PFAIL
DetailsTroy Cobbley
The new 15cd strobe in the corridor is overspaced. Also notification needs to be extended into the corridor in front of the restrooms since the door that is shown on the building plans has not been installed. No testing was actually performed. All other spacing within the tenant space appears ok. Tim and I discussed options.