Permit Information
Permit NumberFIR13-00030
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 11005 W FAIRVIEW AVE
Project NameNapa Auto Parts Fairview
Customer Number 
ePlanReviewYes
Description
Install wet pipe system throughout the new building with ceiling sprinklers at the deck and a second level below the rack mezzanine.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/29/20134/30/20134/30/2013APASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in4/29/20134/30/20134/30/2013APASS
DetailsTroy Cobbley
Overhead hydro test and forward flush passed
INSP-Conference4/25/20134/25/20134/25/2013PPASS
DetailsTroy Cobbley
The modified 4" pipe routing below the mezzanine is passed.
INSP-Sprinkler Rough-in4/19/20134/19/20134/19/2013PPASS
DetailsTroy Cobbley
Sprinkler rough-in passed. Baffles are needed between many of the sprinkler heads below the mezzanine since a min. 8'-0" is needed between the heads. Jeff and I discussed options.
INSP-Sprinkler Rough-in4/11/20134/12/20134/12/2013APASS
DetailsTroy Cobbley
Sprinkler piping above hardlids is ok to cover
INSP-Sprinkler Rough-in4/11/20134/11/20134/11/2013PCANC
DetailsTroy Cobbley
Overbooked. Troy is going to reschedule