Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR13-00081
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1072 N LIBERTY ST
Project NameSARMC Women & Children Outpati
Customer Number 
ePlanReviewYes
Description
This fire alarm permit is to add notification devices with the necessary power supplies, adding duct detectors for heat pump units shut down and in-duct detectors for fire smoke dumpers close. Tie in to Existing FA system.
Associated building permit: BLD12-03126
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/6/20136/7/20136/7/2013APASS
DetailsTroy Cobbley
Permit finaled. I had the contractor change the horn strobe in the first floor restroom to a strobe only to solve a sync problem.
INSP-Final Inspection6/5/20136/6/20136/6/2013AFAIL
DetailsTroy Cobbley
Need all of the notification circuits tested and updated as-builts provided prior to a final sign off.
INSP-Final Inspection6/4/20136/5/20136/5/2013AFAIL
DetailsTroy Cobbley
Testing continued today on the induct detectors on the first floor that control the hvac system and fire smoke dampers. See the city approved plans for devices marked "ok" in red.
INSP-Alarm Testing5/31/20136/3/20136/3/2013ADONE
DetailsTroy Cobbley
Finished the fire/smoke dampers on the second floor. Also performed walk through of the first floor to address any potential problems. It appears plan modifications will be needed due to additional initiating devices, additional notification devices, relocated initiating devices and NAC panels.
INSP-Alarm Testing5/30/20135/31/20135/31/2013ADONE
DetailsTroy Cobbley
Todays inspection was for the second floor. We verified spacing on all audio/visuals. Found several tht needed adjustment. Also five horns need to be changed to horn/strobes due to ceiling obstructions. Testing of the duct smoke detectors for hvac shutdown passed. It appears the fire/smoke dampers are wired backwards and access may be limited on some which will need to be addressed prior to the next inspection.
INSP-Alarm Testing5/30/20135/30/20135/30/2013AFAIL
DetailsTroy Cobbley
No approved plans on site. We all agreed to reschedule for tomorrow morning.