Permit Information
Permit NumberFIR13-00095
StatusFinaled
Name CURTIS FIRE SPRINKLER SERVICE INC
Site Address 6125 W FAIRVIEW AVE
Project NameSALON EDEN
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of protecting a restaurant with a new wet pipe system. The system is supplied through 4” underground, to a 2½” backflow preventer and riser. There is a remote 2½” FDC. The system is looped with varying pipe sizes. There is a small basement protected with one line of sprinklers.

Contractor Note: The City of Boise now has the capabilities to accept electronic plan submittals.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/24/20139/25/20139/25/2013PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection9/23/20139/23/20139/23/2013PCANC
DetailsTroy Cobbley
Duplicate inspection
INSP-Final Inspection9/20/20139/23/20139/23/2013AFAIL
DetailsTroy Cobbley
The "well" needs to be installed at the FDC riser and provide tag for the backflow preventor and a head wrench.
INSP-Final Inspection8/20/20138/21/20138/21/2013AFAIL
DetailsTroy Cobbley
I stopped at the job site and found that the "well" has not been installed at the FDC as discussed. I also noted the signage at the bell is missing. I left Don a voice message.
INSP-Final Inspection8/1/20138/5/20138/5/2013PCANC
DetailsTroy Cobbley
don Phone #: ###-####
INSP-Supply line flush7/29/20137/29/20137/29/2013PPASS
DetailsTroy Cobbley
Underground flush passed
INSP-Sprinkler Rough-in/Hydro7/19/20137/22/20137/22/2013APASS
DetailsTroy Cobbley
Overhead hydro test passed. I noted that the fire dept connection has not been installed on the street side of the building. I spoke with Don and he is going to contact Tim Frost to verify an approved location for the fdc and the electric alarm bell.
INSP-Supply line flush7/19/20137/22/20137/22/2013ACANC
DetailsTroy Cobbley
Cancel per Don Phone #: ###-####
INSP-Sprinkler Rough-in7/18/20137/19/20137/19/2013APASS
DetailsTroy Cobbley
Rough-in now matches the plan modification.
INSP-Sprinkler Rough-in/Hydro4/29/20134/29/20134/29/2013PFAIL
DetailsTroy Cobbley
Due to extensive routing modifications, swing joints and additional sprinkler heads plan modifications will be needed for this project. Don is going to provide verification the pipe straps and screws are listed for hanging the 2" mains. Siesmic restraints are required for the branchlines. There is wood at the top of the old fire place so sprinkler protection as per the plans will be required. There appears to be an addtional combustible concealed space near the kitchen that will need sprinkler protection.
INSP-Sprinkler Rough-in/Hydro3/25/20133/27/20133/27/2013APASS
DetailsTroy Cobbley
Todays inspection was an approval to cover the underground supply piping and an approval for the underground supply piping hydro test. I let Don know that as-builts showing the two additional 4" elbows will be required at the end of the project.