Permit Information
Permit NumberFIR13-00100
StatusFinaled
Name TYCO INTEGRATED SECURITY
Site Address 111 N CURTIS RD
Project NamePeasley Transfer & Storage
Customer Number 
ePlanReviewYes
Description
This fire alarm permit is to replace the existing old Notifier panel and slave dialer with a new Unimode 9050 addressable FACP with built-in DACT. Install 2 duct smoke detectors, smoke detector above control unit, pull station, connect to the existing sprinkler switches, and install an annunciator at the warehouse entry door by the knox box. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/8/20135/10/20135/10/2013PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection4/23/20134/26/20134/26/2013AFAIL
DetailsTroy Cobbley
Wire the duct smoke detectors to shut down the hvac units immediatley per IMC, resend signals for the tamper switches to verify "supervisory" signals are sent to central station and provide map and close out documents.