INSP-Final Inspection | 7/25/2013 | 7/26/2013 | 7/29/2013 | P | PASS |
Forrest France
|
|
|
Previously noted correction items verified for completion. Fire alarm permit finaled.
|
INSP-Final Inspection | 7/18/2013 | 7/23/2013 | 7/29/2013 | P | FAIL |
Forrest France
|
|
|
Final pending additional coverage at adjoining guestrooms 312/314, room smokes to report as a supervisory condition, provide as-builts reflecting actual ADA room locations and correct CO addresses, post points map at the panel.
|
INSP-Final Inspection | 7/15/2013 | 7/16/2013 | 7/16/2013 | A | FAIL |
Forrest France
|
|
|
Need to provide WP notification devices at the guest room bathrooms per review notes, HT supervision and CO devices are not yet installed, field install does not correlate to the approved plan with regard to which rooms are ADA/hearing impared and provided with visual coverage, wall mount notification appliances should not be installed in a ceiling mount position. No testing performed due to modifications and adjustments necessary.
|