Permit Information
Permit NumberFIR13-00141
StatusFinaled
Name SENTRY SECURITY SYSTEMS
Site Address 2879 S FRY ST
Project NameBoise Rigging
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to replace the existing fire alarm system due to instability of an old system. This permit scope of work includes sprinkler system monitoring, elevator recall and shunt trip functions, smoke and heat detectors for recall/shunt trip functions, a smoke detector above the FACP, a pull station, and a remote annunciator panel. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/3/20135/6/20135/6/2013APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection4/28/20134/29/20134/29/2013PFAIL
DetailsTroy Cobbley
The hvac unit in the second floor sewing room failed to shutdown when the duct smoke detector was activated. The flow switch alarms do not latch as required and the outside electric alarm bell did not function. Per Robert the 5 year elevator inspection is going to require the fire mans hat to function correctly. He would like to waite until this elevator work is complete prior to testing/finaling this permit.
INSP-Final Inspection4/11/20134/11/20134/11/2013PFAIL
DetailsTroy Cobbley
Items tested include the phone lines, sprinkler tamper switches and elevator recall. Items needed to be approved through plan review is that the firemans hat can flash when a lobby smoke detector is activated (per code it is not allowed). Also when the wharehouse smoke detector is activated the doors open to the retail side not recall to the second floor. The duct detectors do shut down the hvac units but per Robert are wired wrong. He is going to correct this item and retest. There is one additional tamper switch not shown on the plans and the possiblility of deleting a module at the elevator. These changes will need to be shown on as-builts. I notified the building owner that the annual inspections of the sprinkler systems was overdue. He made a phone call to get the work scheduled.