INSP-Final Inspection | 1/15/2014 | 1/16/2014 | 1/16/2014 | A | PASS |
Forrest France
|
|
|
Correction items completed. Fire alarm permit approved for final status.
|
INSP-Final Inspection | 1/14/2014 | 1/15/2014 | 1/15/2014 | A | CANC |
Forrest France
|
|
|
As early as possible Phone #: 2089411846 >> Inspection requested via mobile web by Brian Aa Inspection cancelled via mobile web on Wednesday, January 15, 2014.
|
INSP-Final Inspection | 11/22/2013 | 11/25/2013 | 11/25/2013 | A | PART |
Forrest France
|
|
|
Final pending plan modification approvals and inspection for relays to existing fire smoke dampers to remain functional at the east garage.
|
INSP-Final Inspection | 11/20/2013 | 11/21/2013 | 11/25/2013 | A | FAIL |
Forrest France
|
|
|
Inspection completed 11/21. SD at the elevator lobbies in the new parking garage will not meet listing due to missing HVAC. Provide verification existing fire/smoke dampers are not required or interface with panel per plan. Provide a plan modification due to necessary changes.
|