INSP-Final Inspection | 5/29/2013 | 6/3/2013 | 6/3/2013 | A | PASS |
Forrest France
|
|
|
Noted correction items verified for completion, plan modifications recieved, final inspection passed. Fire alarm permit finaled.
|
INSP-Final Inspection | 5/15/2013 | 5/17/2013 | 5/17/2013 | A | FAIL |
Forrest France
|
|
|
Correction notice items include; provide WP notification appliances at rooms 118 and 119, MP at the riser needs to be between 42" and 48" AFF per note #33, new wall at hall 111 will require additional coverage, remove existing A/V at the fire riser room, post accurate points map at the panel per note # 51, post signage per note #53, relay for sound system shutdown did not function. Plan modification needed due to six existing duct detectors and one hood monitor not included on approved plans. Revise matrix to include sound relay. Revise one-line diagram to include all building duct detectors and initiating devices.
|