Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR13-00204
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 3233 N COLE RD
Project NameWalMart Neighborhood Market
Customer Number 
ePlanReviewYes
Description
Demo all existing sprinkler system back to the flange above floor. Reinstall new fire sprinkler systems per the engineered drawings provided by Henderson Engineers Inc.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/9/20139/10/20139/11/2013APASS
DetailsForrest France
Forward flow testing completed satisfactory.
INSP-Final Inspection9/6/20139/9/20139/9/2013PDEFR
DetailsForrest France
Please call 1/2 hr prior to inspection. Mike B is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
INSP-Final Inspection9/5/20139/6/20139/6/2013PFAIL
DetailsTroy Cobbley
Need forward flush to final.
INSP-Sprinkler Rough-in/Hydro8/14/20138/16/20138/16/2013PPASS
DetailsTroy Cobbley
The overhead hydro test passed
INSP-Sprinkler Rough-in/Hydro8/9/20138/12/20138/12/2013AFAIL
DetailsTroy Cobbley
Hydro test failed due to a visible drop in pressure at the guage. Also sprinkler coverage has not been installed under an overhead door. This work will need to be done prior to a hydro test.
INSP-Sprinkler Rough-in/Hydro8/8/20138/9/20138/9/2013PNR
DetailsForrest France
Hydrostatic test incompleted due to system leakage in need of repair.
INSP-Sprinkler Rough-in8/2/20138/5/20138/5/2013APART
DetailsTroy Cobbley
The retail area ceilings are ok to cover piping. I noted one location where pendant mount lighting is blocking the pendant sprinkler heads. The three time rule of NFPA 13 chapter 8 should apply.
INSP-Sprinkler Rough-in7/22/20137/23/20137/23/2013APASS
DetailsTroy Cobbley
Todays inspection was to verify that the insulation had been repaired at the deck and was no longer obstructing the upright sprinkler heads. All areas had been repaired except for three locations. I will verify these three at the next rough-in inspection.
INSP-Sprinkler Rough-in7/3/20137/5/20137/5/2013APART
DetailsTroy Cobbley
Todays inspection was for the hangers and piping which passed except Nate is going to add two branchline restraints for me. A separate inspection will be needed for approval to cover. As of today insulation is blocking the upright sprinkler coverage in many locations and the ceiling "t bar" has not been installed yet to verify actual pendant head layout.
INSP-Sprinkler Rough-in7/2/20137/3/20137/3/2013ACANC
DetailsTroy Cobbley
Cancel per Nate
INSP-Sprinkler Rough-in6/18/20136/19/20136/19/2013PPART
DetailsForrest France
Okay to cover ceilings at the mens, womens, family and pharmacy restrooms as marked and dated on stamped plans. Discussed coverage at the coolers, UG fire supply flush post demo.
INSP-Sprinkler Rough-in6/14/20136/17/20136/17/2013APART
DetailsForrest France
Overhead work okay to cover at the cash room and entry vestibule.
INSP-Sprinkler Rough-in6/13/20136/14/20136/14/2013PFAIL
DetailsForrest France
Inspection for sheetrock ceiling cover at the cart storage and cash rooms only- Draft stop above the cart storage area ceiling creates an obstruction to upright sprinkler coverage, noted mixed temp. heads are installed at the cart storage room absent of a specific heat source, missing approved plans on site.