Permit NumberFIR13-00230
StatusFinaled
Name TRIBAL FIRE SYSTEMS
Site Address 770 W MAIN ST
Project NameCapitol Terrace Parking Garage
Customer Number 
ePlanReviewYes
Description
Contractor to replace existing Black Sprinkler Pipe with new Galvanized Pipe. Start point is after existing Dry Pipe Valve. Replace existing 250gpm booster pump to 300gpm booster pump
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/23/20139/24/20139/25/2013PPASS
DetailsForrest France
Reinspection completed satisfactory. First floor dry system trip test passed after corrections made.
INSP-Sprinkler Rough-in/Hydro9/11/20139/12/20139/12/2013PFAIL
DetailsForrest France
Time limitations per NFPA 13 for dry system water delivery were exceeded for the 1st floor system.
INSP-Sprinkler Rough-in/Hydro9/11/20139/12/20139/12/2013APART
DetailsForrest France
Completed hydrostatic testing of the new dry system piping at the 4th, 5th floors, and riser.
INSP-Sprinkler Rough-in/Hydro9/5/20139/9/20139/12/2013PPART
DetailsForrest France
Completed acceptable fire pump testing per NFPA 20 guidelines.
INSP-Sprinkler Rough-in/Hydro9/11/20139/11/20139/12/2013PPART
DetailsForrest France
Completed satisfactory hydrostatic testing for the new dry system piping at the 1st, 2nd, and 3rd, floors. Also verified previous correction items are finished or underway.
INSP-Sprinkler Rough-in/Hydro9/9/20139/10/20139/11/2013PNR
DetailsForrest France
Hydro for systems Phone #: ###-#### >> Inspection requested via web by John Venche
INSP-Sprinkler Rough-in/Hydro8/30/20139/5/20139/6/2013ANR
DetailsForrest France