Permit Information
Permit NumberFIR13-00268
StatusFinaled
Name MOUNTAIN ALARM
Site Address 2500 S VISTA AVE
Project NameExtended Stay America
Customer Number 
ePlanReviewNo
Description
Complete replacement of fire alarm system due to failure of existing system including replacement of all initiating and notification devices. No associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/7/201311/7/201311/7/2013PPASS
DetailsForrest France
Verified points map has been posted, recieved record of completion forms. Fire alarm permit finaled.
INSP-Alarm Testing8/29/20139/4/20139/5/2013PPART
DetailsForrest France
Completed remainder of functional testing including occupant notification, EOL, descriptors for the second floor initiating devices, ADA room coverage. One HS repaired while on site. Final pending points map to be posted at the panel per agreement.
INSP-Final Inspection8/28/20138/29/20138/29/2013APART
DetailsForrest France
Items tested today include all MP stations, SD at the common, public and employee work areas on both the first and second floors, riser supervision, elevator recall and machine room functions, RA. Verified previous correction items are finished with the exception of a points map at the panel and ADA room coverage. Need to provide descriptors for all second floor initiating devices. Notification testing to be scheduled in advance as discussed with contractor and building manager on site.
INSP-Final Inspection8/26/20138/27/20138/27/2013PCANC
DetailsTroy Cobbley
Overbooked. I spoke to ray about rescheduling. Phone #: ###-####
INSP-Final Inspection8/6/20138/9/20138/9/2013AFAIL
DetailsForrest France
Completed initial walkthrough. Items noted include; provide a MP at stairway #2 second floor exit door, visual notification at ADA rooms to meet guidelines per NFPA 72 table 18.5.4.6.2, adjust cd settings at notification appliances in mech. room 130 and facilities room 137, post signage at the door leading to the FACP per review note #25, post points map including location of the CO detectors, relocate HD at the elevator machine room, provide for shunt trip and include revision on operations matrix. Functional testing pending corrections and adjustments.
FIR-Aging Inspection8/6/20138/9/20138/9/2013ADONE
DetailsForrest France
Duplicate inspection request
INSP-Conference7/9/20137/9/20137/9/2013PDONE
DetailsForrest France
Regarding project completion to date
INSP-Alarm Testing7/2/20137/3/20137/3/2013PNR
DetailsForrest France
On site visit to determine status of work in progress- FACP and NAC's installed, occupant notification verified at the first and second floors, offsite monitoring included. Noted missing MP at the 2nd floor stairway #2. Project not in condition for final acceptance testing at this time.