Permit Information
Permit NumberFIR13-00348
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 300 S CAPITOL BLVD
Project NameRetail 1 Capitol & Front
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of a 2 double tree dry system with telescoping branch piping, 4” mains,6” riser and 6” backflow preventer.

The underground piping is under permit FIR13-00248
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/10/201310/11/201310/11/2013APASS
DetailsCraig D. Hanson
INSP-Sprinkler Rough-in/Hydro10/3/201310/4/201310/4/2013APART
DetailsForrest France
Concluded satisfactory 24 hr. air test within allowable pressure loss per NFPA13.
INSP-Sprinkler Rough-in10/1/201310/2/201310/3/2013PPART
DetailsForrest France
Overhead hydrostatic testing completed okay
INSP-Sprinkler Rough-in10/2/201310/3/201310/3/2013APART
DetailsForrest France
Begin 24 hr. air test of the overhead dry system at 11:15AM @41psig.
INSP-Sprinkler Rough-in9/25/20139/26/20139/26/2013APASS
DetailsCraig D. Hanson
Rough in pass-still need to look at riser and bracing for riser before cover.
INSP-Supply line flush9/4/20139/5/20139/6/2013PDEFR
DetailsForrest France
Water supply not yet available to complete flushing per contractor.
INSP-Supply line flush9/5/20139/6/2013 P 
DetailsForrest France
Nate is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus