Permit Information
Permit NumberFIR13-00453
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 5253 W KENDALL ST
Project NameBAGLEY KENDALL
Customer Number 
ePlanReviewYes
Description
This permit is to install approximately 235' of 8" C-900 underground piping with associated fittings and thrust blocks.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/25/201310/25/201310/25/2013PPASS
DetailsForrest France
UG fire supply line permit okayed for final.
INSP-Supply line flush10/24/201310/25/201310/25/2013APART
DetailsForrest France
UG fire supply line flush completed satisfactory.
INSP-Sprinkler Rough-in/Hydro10/4/201310/4/201310/4/2013PPASS
DetailsTroy Cobbley
Underground hydro test passed
INSP-Final Inspection10/2/201310/3/201310/3/2013APASS
DetailsTroy Cobbley
IBR cover inspection passed
INSP-Sprinkler Rough-in10/2/201310/2/201310/2/2013PPASS
DetailsTroy Cobbley
Remaining underground supply line piping is ok for cover except for the IBR (need to see thrust block).
INSP-Sprinkler Rough-in10/1/201310/1/201310/1/2013PPART
DetailsTroy Cobbley
The underground supply line from the street to the first fitting is ok to cover.