Permit NumberFIR13-00514
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 64 N COLE RD
Project NameIdaho Aquarium Expansion
Customer Number 
ePlanReviewYes
Description
Idaho Aquarium project is to add notification devices; we are adding a new NAC panel trigger by an existing FACP. We are adding 9 ceiling horn strobes over the exhibition areas and 4 ceiling strobes on the public bathrooms. Associated with building permit BLD12-03324. (IDAHO AQUARIUM - EXPANSION) Fire sprinkler system used for building area increase and for fire area. To expand an existing 9,264 square foot tenant space into an adjacent 4,597 square foot area. After the expansion, this tenant space will have a total floor area of about 13,861 square feet and an assembly occupant load of 393. The first permit for the Idaho Public Aquarium was BLD11-01835 and the second was BLD12-00811. The use of this tenant space is for exhibit tours. A total of about 6,480 square feet of floor area will be available for this use. This facility is NOT approved for day camps and/or overnight stays. Site built aquariums are required to comply with the Structural Engineer’s design. Special inspection is required for epoxy anchors, welding, concrete, and masonry. Precautions shall be taken to prevent children from falling into the aquariums. If guards are not provided, sufficient adult supervision is required at all times when children are present. The work is required to comply with the approved drawings, with the structural design, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. **CJW*
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/27/20148/28/20148/28/2014APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection7/31/20148/1/20148/1/2014PFAIL
DetailsTroy Cobbley
Owner wanted us to reschedule due to the crowds. I noted that 14 guage wire was installed not 12 guage as per the approved plans. Also the 75cd ceiling mounted horn/strobes need to have reduced spacing due to the height at which they have been installed. Also the 110cd ceiling moiunt strobe at teh very end of the tenant space is overspaced off of the wall in the picnic table area. And the NAC panel has been relocated to a different location in the building. No actual testing was performed.