INSP-Final Inspection | 4/8/2014 | 4/15/2014 | 4/15/2014 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 3/26/2014 | 3/27/2014 | 3/27/2014 | P | FAIL |
Troy Cobbley
|
|
|
Everything is complete except the unknown signals from zone one need addressed as per the fire dept.
|
INSP-Final Inspection | 2/25/2014 | 2/26/2014 | 2/26/2014 | A | FAIL |
Troy Cobbley
|
|
|
Provide weather proof cover for the annunciator, repair supervisory signal on zone 6 and provide updated map showing zone 1 as a spare and zone 10 being utilized.
|
INSP-Final Inspection | 12/16/2013 | 12/19/2013 | 12/19/2013 | A | CANC |
Troy Cobbley
|
|
|
Cancel per art Phone #: ###-####
|
INSP-Final Inspection | 12/16/2013 | 12/18/2013 | 12/18/2013 | A | FAIL |
Troy Cobbley
|
|
|
NAC circuit 1 has a "open" trouble, there is only one phone line, multiple strobes are overspaced, one strobe is blocked by movable partitions, I need verification that the strobes in the prep rooms are weatherproof and the remote annunciator (located outside) is weather proof, pull station in the crematorium is mounted too high. We did not set off the strobes to check sync. or test any devices since there was a trouble on the system and only one phone line.
|
INSP-Final Inspection | 11/22/2013 | 11/25/2013 | 11/25/2013 | A | FAIL |
Troy Cobbley
|
|
|
No inspection and testing form, no city approved plans or notes. Strobes would not function per Art. No testing performed.
|