Permit NumberFIR13-00519
StatusFinaled
Name TYCO INTEGRATED SECURITY
Site Address 1200 N CLOVERDALE RD
Project NameCloverdale Funeral Home
Customer Number 
ePlanReviewYes
Description
Replacing the existing Edwards Panel, smoke detectors and Annunciator with a New Edwards Panel and Annuciator. The Existing Edwards Panel is Obsolete and is Failing we will be replacing the panel with a Like Panel. No associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/8/20144/15/20144/15/2014APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection3/26/20143/27/20143/27/2014PFAIL
DetailsTroy Cobbley
Everything is complete except the unknown signals from zone one need addressed as per the fire dept.
INSP-Final Inspection2/25/20142/26/20142/26/2014AFAIL
DetailsTroy Cobbley
Provide weather proof cover for the annunciator, repair supervisory signal on zone 6 and provide updated map showing zone 1 as a spare and zone 10 being utilized.
INSP-Final Inspection12/16/201312/19/201312/19/2013ACANC
DetailsTroy Cobbley
Cancel per art Phone #: ###-####
INSP-Final Inspection12/16/201312/18/201312/18/2013AFAIL
DetailsTroy Cobbley
NAC circuit 1 has a "open" trouble, there is only one phone line, multiple strobes are overspaced, one strobe is blocked by movable partitions, I need verification that the strobes in the prep rooms are weatherproof and the remote annunciator (located outside) is weather proof, pull station in the crematorium is mounted too high. We did not set off the strobes to check sync. or test any devices since there was a trouble on the system and only one phone line.
INSP-Final Inspection11/22/201311/25/201311/25/2013AFAIL
DetailsTroy Cobbley
No inspection and testing form, no city approved plans or notes. Strobes would not function per Art. No testing performed.